Biddle SITS-120_UG 电路图.pdf
《Biddle SITS-120_UG 电路图.pdf》由会员分享,可在线阅读,更多相关《Biddle SITS-120_UG 电路图.pdf(37页珍藏版)》请在收音机爱好者资料库上搜索。
1、Part _50377 Date 04/27/1998 INSTRUCTION MANUAL For SECONDARY INJECTION TEST SET Model SITS-120 It is essential that this instruction book be read thoroughly before putting the equipment in service. RadioFans.CN 收音机爱 好者资料库 REVISION HISTORY RevisionECN #Date 004/27/1998 COMMENTS Any comments or sugges
2、tions regarding the use of this test instrument or instruction manual would be appreciated. Send your comments to AVO International, 4271 Bronze Way, Dallas, TX 75237 IMPORTANT The information and data contained within this instruction manual are proprietary with AVO International. The equipment des
3、cribed herein may be protected by one or more U.S. letters patent. AVO INTERNATIONAL specifically reserves to itself all rights to such proprietary information as well as all rights under any such patent, none of which is waived by the submission of this instruction manual to anyone. The recipient,
4、if a Government agency, acknowledges that this instruction book and the equipment described were procured with Limited Rights to technical data as described in ASPR 9-203 (b). Copyright AVO International, 1998 RadioFans.CN 收音机爱 好者资料库 i SAFETY PRECAUTIONS WARNING: VOLTAGES GENERATED BY THIS INSTRUMEN
5、T CAN BE HAZARDOUS This instrument has been designed for operator safety; however, no design can completely protect against incorrect use. Electrical circuits are dangerous and can be lethal when lack of caution and poor safety practices are used. There are several standard safety precautions that s
6、hould be taken by the operator. Where applicable, IEC safety markings have been placed on the instrument to notify the operator to refer to the instruction manual for instructions on safety related topics. Refer to the following table of symbols and definitions. SymbolDescription Direct Current Alte
7、rnating Current Both direct and alternating current Earth (ground) Terminal. The SITS-120 output Ground terminals are connected to chassis ground. Protective Conductor Terminal Frame or Chassis Terminal On (Supply) Off (Supply) Caution, risk of electric shock Caution (refer to accompanying documents
8、) RadioFans.CN 收音机爱 好者资料库 ii SAFETY PRECAUTIONS CONTINUED The following are some specific safety related items associated with the SITS-120 test system. Always start with the power OFF, before connecting the power cord. Make sure outputs are off before attempting to make test connections. Always use
9、 properly insulated test leads. The test leads supplied with the unit are rated for the voltage output ratings of the test system, and should be properly used and cared for. Do not use cracked or broken test leads. Always lift and carry the test set using both carry handles. Improperly carrying the
10、unit by one handle could damage the handle. Always turn the test system off before disconnecting the power cord. Turn outputs off before removing or inserting test leads. UNDER NO CIRCUMSTANCES SHOULD THE OPERATOR PUT HIS HANDS OR TOOLS INSIDE THE TEST SYSTEM CHASSIS WITH THE TEST SYSTEM CONNECTED T
11、O A POWER SOURCE. LETHAL VOLTAGES ARE PRESENT AND MAY CAUSE SERIOUS INJURY OR DEATH! INSTALLATIONCategory II OPERATIONAL SAFETY Every consideration has been given to the design and construction of the Secondary Injection Test Set to make it a safe piece of test equipment as well as one that is accur
12、ate, reliable and easy to use. It must be remembered that the unit is capable of producing voltage and current levels that can be deadly if personnel come in contact with them. The SITS-120 unit should be properly operated and serviced by qualified individuals who have familiarized themselves with t
13、he unit and thoroughly read the instruction manual provided with it. If questions arise concerning care, operation or application of the unit that are not explained in the instruction manual, contact a AVO INTERNATIONAL representative. iii TABLE OF CONTENTS SECTIONPAGE OPERATIONAL SAFETY.ii THEORY O
14、F OPERATION.1 UNIT PANEL ILLUSTRATION.1 DESCRIPTION OF CONTROLS AND INSRUMENTATION.2 INPUT POWER.6 SELECTION OF OUTPUT TERMINALS.7 SERVICE DATA .8 MAINTENANCE INSTRUCTIONS.8 BASIC TROUBLESHOOTING.9 Power Input.9 Timer, Monitor and Battery Simulator Module.10 WARRANTY.13 TEST APPLICATIONS.14 TEST PRO
15、CEDURES.14 TIME DELAY OVERCURRENT DEVICES.14 INSTANTANEOUS ELEMENT OF OVERCURRENT RELAYS.16 TIME DELAY VOLTAGE RELAYS .18 PICKUP and DROPOUT TEST PROCEDURE FOR VOLTAGE CONTROLLED RELAYS .19 GENERAL TEST FOR TIMING OPERATIONS.20 MOLDED CASE CIRCUIT BREAKERS.21 OVERCURRENT ELEMENT OF CIRCUIT BREAKERS.
16、22 INSTANTANEOUS ELEMENT OF CIRCUIT BREAKER.24 MOTOR OVERLOAD RELAYS.26 SPECIFICATIONS.27 OPTIONS AND ACCESSORIES.30 PARTS LIST.31 SCHEMATICS.32 1 THEORY OF OPERATION The AVO Secondary Injection Test Set is a portable, self-contained unit which provide stepless, continuously adjustable current and v
17、oltage outputs. The unit is housed in a rugged, compact suitcase-type thermoplastic enclosure with convenient carry handles and removable cover. The SITS-120 unit incorporates digital metering, crystal-controlled digital timer, and solid-state control circuitry to provide a variety of independently
18、adjustable voltage and current outputs. The dual purpose volt/ammeter will provide a wide variety of accurate, switch-selectable ranges. The independent outputs enable the SITS-120 to provide current or voltage only, or a combination of the two, to meet numerous testing requirements in a wide variet
19、y of test applications. The main AC current output has selectable output ranges of 5 Amperes 0 - 140 Volts; 10 Amperes 0 - 70 Volts; 25 Amperes 0 - 40 Volts and 120 Amperes 0 - 5 Volts. The voltage outputs are switch selectable, either AC or DC, with a range of 0 - 240 Volts. UNIT PANEL ILLUSTRATION
20、 2 DESCRIPTION OF CONTROLS AND INSTRUMENTATION DESCRIPTION OF FEATURES POWER ON/OFF Switch and Input Power Connection (1): The switch controls all the input power to the unit, but no output is available until the unit is initiated. Power on is indicated by the meter displays which light up when the