1、AVTM21-415Ja Rev A June 2005 15 kV Megohmmeter Test Set Catalog No. 210415 Series High-Voltage Equipment Read the entire manual before operating. Aparato de Alto Voltaje Antes de operar este producto lea este manual enteramente. 2621 Van Buren Avenue Norristown, PA 19403 1-800-723-2861 ext. 8578 Rad
2、ioFans.CN 收音机爱 好者资料库 15 kV Megohmmeter Test Set Catalog No. 210415 Series M RadioFans.CN 收音机爱 好者资料库 Copyright 1989-2005 by Megger. All rights reserved. The information presented in this manual is believed to be adequate for the intended use of the product. If the product or its individual instrument
3、s are used for purposes other than those specified herein, confirmation of their validity and suitability must be obtained from Megger. Specifications are subject to change without notice. M Valley Forge Corporate Center 2621 Van Buren Avenue Norristown, PA 19403-2329 USA Tel: 610-676-8500 Fax: 610-
4、676-8610 RadioFans.CN 收音机爱 好者资料库 i AVTM21-415Ja Rev. A June 2005 Table of Contents 1 INTRODUCTION.1 2 SAFETY PRECAUTIONS.3 3 RECEIVING INSTRUCTIONS.5 4 SPECIFICATIONS.7 5 DESCRIPTION.13 6 CONTROL 50 Hz, reduced rating Basis of Rated Performance: 230 Volt 60 Hz supply with stabilizer out. M 8 AVTM21-
5、415Ja Rev. A June 2005 OUTPUT TEST VOLTAGE: 0-15 kV dc, negative with respect to ground. OUTPUT CURRENT: With Stabilizer Out at 60 Hz: 2 mA continuous; 5 mA for 12 minutes. at 50 Hz: 1.67 mA continuous; 4.17 mA for 12 minutes. With Stabilizer In at 50 or 60 Hz: At 15 kV, 50 A continuous. Short Circu
6、it: 12 mA maximum, limited by circuit breaker. RIPPLE VOLTAGE (rms) 1% at 3 M resistive load OUTPUT VOLTAGE REGULATION: Internal Stabilizer Out: 13% no load to 7.5 M load % percent change in line voltage Internal Stabilizer In: 0.1% no load to 300 M load including 10% line voltage change METERING: K
7、ilovoltmeter: 4 inch (11.4 cm) Taut-Band. 3 color-coded scales: 0-7.5 kV (red), 0-15 kV (black) and 0- 1.5 reference (green). Accuracy: 2% full scale. Megohmmeter: 4 inch (11.4 cm) Taut-Band. 2 scales: 1-100 Megohms (red), 2-200 Megohms (black). Accuracy: 2% of full scale length at any marking, bett
8、er near high resistance end. Ranges: 8 ranges, 4 per scale, as described in following Table. SPECIFICATIONS 9 AVTM21-415Ja Rev. A June 2005 MEGOHMMETER SPAN, MEGOHMS VOLTMETER RANGE SETTING VOLTAGE kV RANGE SWITCH at x 1 RANGE SWITCH at x 10 RANGE SWITCH at x 100 RANGE SWITCH at x 1K 15 10 2-200 20-
9、2000 200- 20,000 2000- 200,000 7.5 5 1-100 10-1000 100- 10,000 1000- 100,000 EITHER ANY up to 300 up to 3000 up to 30,000 up to 300,000 CONTROLS Power OFF-ON switch (Circuit Breaker) with green lamp indicator. High Voltage OFF-ON switch (Circuit Breaker) with red lamp indicator. Voltage control with
10、 Zero-Start interlock, 0-100 reference dial. Stabilizer selector switch: IN-OUT. Voltmeter Range Switch: 7.5-15 kV. Megohmmeter multiplier switch, 4-position: x1, x10, x100, x1K M 10 AVTM21-415Ja Rev. A June 2005 CABLES AND CONNECTORS Input Cable: Attached; 5 feet (1.5 meters), 3-wire with plug. Out
11、put Cable: Attached; shielded with GUARD terminal, high voltage clip and boot; 15 feet (4.6 meters) long. Ground Cable: Separate, 10 feet (3.3 meters) with positive action clamp at outboard end. Ground Terminal: inch stud with wing nut. External Instrument Jack: Accepts -inch 2-wire phone plug for c
12、onnecting external recorder or current meter to read current in test item. PHYSICAL Case: High-impact structural foam, polycarbonate plastic with metal control panel and removable hinged lid Size: Overall Width Depth Height 20 1/8 12 13 inches 52 20.5 33 cm Weight: Cat. No. 210415: 35 lbs. (15.9 kg)
13、 Cat. No. 210415-47: 37 lbs. (16.8 kg) Instruction Card: Permanently attached inside lid. Cable R4 and R5 for X10; R4, R5, R6 and R7 for X100. No shunt is used for X1K range. In series with M102 is a two-wire phone jack J1 that is shorted unless a plug is inserted. For use see Section 9. For the use
14、 and significance of the guard see Sections 9 and 10. The Test Set is energized directly by W1 with the green wire tied directly to the panel to provide a panel ground. The white neutral wire is uninterrupted and is considered the return path for the Test Set supply. The black wire is considered hot
15、 and power is fed to the set via the CB1 circuit breaker that also is DESCRIPTION 15 AVTM21-415Ja Rev. A June 2005 used as the power-on switch. When power is available and CB1 is closed the green ac ON lamp comes on. The path is interrupted by the contact of K2. Moving the voltage control T1 to zero
16、 closes the contacts of the zero start switch. This action applies the line voltage to the coil of K2 and ultimately to T1. The red HIGH VOLTAGE ON lamp lights since it parallels the coil of K2. Relay K2 will now remain closed even if the voltage control is advanced off its zero position. The line v
17、oltage is fed to T1 through the stabilization selector switch S1, directly when S1 is closed in the OUT position. Raising the voltage control now applies a controlled voltage to the primary of T101 through the trip coil of circuit breaker switch CB2. When S1 is set to the IN position (stabilized) vo
18、ltage is applied to T1 through resistor R1 and a parallel path exists from the input of T1 to the circuit return through the back-to- back connected Zener diodes CR1 and CR2. These diodes clip the peaks of the voltage across T1 so that any transient changes in the line supply voltage do not change t
19、he crest amplitude. This stabilizes the output voltage as long as the load current does not exceed 50 A. The 50 A limit is equivalent to 300 Megohms at 15 kV. Power Supply Option Test sets equipped with the -47 optional input differ from standard sets in that separate step-down transformers T2 and T
20、3 are included between the power source and the Test Set. The nominal line voltage is specified at purchase. Transformers are located in the cover of the Test Set. Optional output voltages may be selected in accordance with the table on the schematic Figure 2. M 16 AVTM21-415Ja Rev. A June 2005 Figu
21、re 2: Schematic Diagram of the 15 kV Megohmmeter 17 AVTM21-415Ja Rev. A June 2005 6 CONTROL references listed in Sections 9 and 10. Place guard connections on the terminals if a guarded test is required. (See Sections 8 and 9). Set up barriers or use other means to keep unauthorized personnel away f
22、rom all high voltage terminals of the complete test arrangement. SELECTION OF LOCATION Select a location for the Test Set which meets the following conditions: 1. The operating area must be as dry as possible. M 20 AVTM21-415Ja Rev. A June 2005 2. The Test Set must be within 10 feet of the high-volt
23、age terminal of the apparatus to be tested. NOTE: For operator safety, the output cable should be fully extended to provide maximum distance between the operator and the high-voltage terminal. 3. A reliable ground connection must be within 12 feet of the Test Set. 4. If an electrical service outlet