1、AVTM246100B Revision B June 2003 Instruction Manual AVTM246100B for Battery Ground Fault Tracer Patent No. 4,546,309 HIGH-VOLTAGE EQUIPMENT Read this entire manual before operating. APARATO DE ALTO VOLTAJE Ante de operar este producto lea este manual enteramente. M Valley Forge Corporate Center 2621
2、 Van Buren Avenue Norristown, PA 19403 U.S.A. 610-676-8500 (Telephone) 610-676-8610 (Fax) RadioFans.CN 收音机爱 好者资料库 RadioFans.CN 收音机爱 好者资料库 Battery Ground Fault Tracer Instruction Manual RadioFans.CN 收音机爱 好者资料库 Copyright 2003 by Megger. All rights reserved. The information presented in this manual is
3、believed to be adequate for the intended use of the product. If the product or its individual instruments are used for purposes other than those specified herein, confirmation of their validity and suitability must be obtained from Megger. Refer to the warranty information below. Specifications are
4、subject to change without notice. WARRANTY Products supplied by Megger are warranted against defects in material and workmanship for a period of one year following shipment. Our liability is specifically limited to replacing or repairing, at our option, defective equipment. Equipment returned to the
5、 factory for repair must be shipped prepaid and insured. Contact your Megger representative for instructions and a return authorization (RA) number. Please indicate all pertinent information, including problem symptoms. Also specify the serial number and the catalog number of the unit. This warranty
6、 does not include batteries, lamps or other expendable items, where the original manufacturers warranty shall apply. We make no other warranty. The warranty is void in the event of abuse (failure to follow recommended operating procedures) or failure by the customer to perform specific maintenance a
7、s indicated in this manual. M Valley Forge Corporate Center 2621 Van Buren Avenue Norristown, PA 19403 U.S.A. 610-676-8500 (Telephone) 610-676-8610 (Fax) i Contents 1 INTRODUCTION.1 About the BGFT.1 How the BGFT Works.2 Applications for the BGFT.2 Upon Receipt of the BGFT.3 Safety First.4 How to Use
8、 This Manual.4 Typographic Conventions.4 2 SAFETY.5 Overview.5 Connection to Power Source.6 Fuse Replacement.7 3 CONTROLS, INDICATORS AND CONNECTORS.9 Overview.9 Transmitter (Figure 2).10 Receiver (Figure 4).12 Current Probe.13 4 OPERATION.15 General.15 Transmitter Connections.16 Applying Transmitte
9、r Power.17 Applying Transmitter Test Voltage.18 Receiver Connections and Applying Power.19 Defining The Fault.20 Bridge Operation.21 Tracing The Fault.22 Instrument Shutdown Procedure.22 5 APPLICATION NOTES.23 6 MAINTENANCE the other items are housed in a separate accessories bag. The Battery Ground
10、 Fault Tracer locates ground faults in ungrounded dc battery systems. Various standards require action when the impedance between any battery polarity and earth ground falls below a specified limit. In the case of nuclear-fueled plants, the Nuclear Regulatory Commission (NRC) requires audits and app
11、ropriate action when this impedance is deemed unsafe. Other facilities come under the guidelines of the National Electric Code, NFPA, IEEE standards, and OSHA requirements for safe operation of dc battery systems in an ungrounded environment. M 2 AVTM246100B Rev B June 2003 How the BGFT Works The Ba
12、ttery Ground Fault Tracer applies a 20 Hz signal between the battery bus and station ground. This is accomplished by connecting the transmitter via the source leads to an accessible battery bus and to a ground bus located in a distribution cabinet. A two-step process then begins to identify both the
13、 magnitude and location of the fault. First, suspect feeder cables are identified by measuring the flow of fault current to ground on all the output circuits from the cabinet, and then a bridge balance measurement is performed to determine the value of capacitance and resistance of the suspected gro
14、und fault. The resistance and capacitance bridge located on the transmitter is used to determine the value of the fault impedance in real and imaginary terms (resistance and capacitive reactance) while the amplitude of the signal current injected into the suspect feeder cable is monitored with the r
15、eceiver. Three stages of amplification can be selected to identify and find faults to 399 k. The red feedback wire (supplied) is used as a canceling feature for the injected signal as compared with the bridge selected impedance. Isolating the fault to a specific location may require moving the equip
16、ment downstream in a distribution system. Once a fault resistance is quantified, the bridge and feedback portion of the procedure can be dismissed and the fault can be tracked by evaluating feeder lines of a subpanel. If the current value decreases after several steady or increasing readings, then t
17、he location is in the opposite direction. Applications for the BGFT The BGFT, Battery Ground Fault Tracer, can find ground faults in ungrounded battery systems in: ? Substations ? Generating Stations ? UPS Systems ? Any other ungrounded dc system For information about other installations that might
18、benefit from impedance testing, contact Megger. INTRODUCTION 3 AVTM246100B Rev B June 2003 Upon Receipt of the BGFT Check the equipment received against the packing list to ensure that all materials are present. Notify Megger of any shortage. Telephone (610) 676-8500. Examine the instrument for dama