Biddle 5kV-DiagnosticTesting 电路图.pdf
《Biddle 5kV-DiagnosticTesting 电路图.pdf》由会员分享,可在线阅读,更多相关《Biddle 5kV-DiagnosticTesting 电路图.pdf(41页珍藏版)》请在收音机爱好者资料库上搜索。
1、RadioFans.CN 收音机爱 好者资料库 MEGGER Insulation Testers1 NOTES Table of Contents INTRODUCTION. 2 WHAT IS INSULATION? . 3 What Causes Insulation to Degrade? . 3 Electrical Stress . 3 Mechanical Stress. 3 Chemical Attack. 3 Thermal Stress . 4 Environmental Contamination . 4 How Can Predictive Maintenance He
2、lp Me? . 4 The Benefit of New Technology. 5 HOW INSULATION RESISTANCE IS MEASURED. 6 How an Insulation Resistance Tester Operates. 6 Components of Test Current. 6 Capacitive Charging Current . 6 Absorption or Polarization Current . 6 Surface Leakage Current. 7 Conduction Current. 7 Connecting your I
3、nsulation Tester. 8 Selected Typical Connections. 9 Shielded Power Cable . 9 Circuit Breaker/Bushings. 9 Power Transformer . 10 AC Generator. 10 Insulation Resistance Tester Scale. 11 Voltage Characteristics. 12 EVALUATION AND INTERPRETATION OF RESULTS. 13 Interpretation of the Infinity () Reading.
4、13 DIAGNOSTIC HIGH VOLTAGE INSULATION TESTS. 15 Spot Reading Test. 15 Time vs. Resistance Test . 17 Polarization Index Test . 18 Step Voltage Test . 20 Dielectric Discharge Test. 21 Different Problems/Different Tests. 23 APPENDICES. 24 Potential Sources of Error/Ensuring Quality Test Results . 24 Te
5、st Leads. 24 Making Measurements above 100 G . 24 Accuracy Statements . 24 Delivery of Stated Voltage . 24 Interference Rejection. 25 Rules on Testing and Comparing. 25 The Guard Terminal . 26 Effects of Temperature . 28 Effects of Humidity . 31 Ingress Protection . 31 High Potential Testing. 33 Cur
6、rent (nA) Readings vs. Resistance (M) Readings . 33 Burn Capability . 34 Drying out Electrical Equipment . 34 Test Item Discharge. 36 Charging Time for Large Equipment . 36 Motor Driven Insulation Testers. 37 5-kV Insulation Testers Available from AVO International . 38 Distributor: MeterCenter Unit
7、ed States: 1-800-230-6008 1-480-659-8351 www.MeterC First Edition: June 2002 2002 AVO International DEDICATION Dedicated to the late T.A. “Ted” Balaska, who pro- vided significant help in structuring this booklet. Ted was an expert in the field of insulation and insu- lation testing and, more import
8、ant, a good friend. AUTHORS David O. Jones Jeffrey R. Jowett S. Graeme Thomson David S. Danner RadioFans.CN 收音机爱 好者资料库 2A Guide to Diagnostic Insulation Testing Above 1 kV NOTESINTRODUCTION Electrical insulation degrades over a period of time because of various stresses, which are imposed upon it du
9、ring its normal working life. The insulation has been designed to withstand these stresses for a period of years, which would be re- garded as the working life of that insulation. This often runs into decades. Abnormal stresses can bring about an increase in this natural aging process that can sever
10、ely shorten the working life of the insulation. For this reason it is good practice to perform regular testing to identify whether increased aging is taking place and, if possible, to identify whether the effects may be reversible or not. The purpose of diagnostic insulation testing is: To identify
11、increased aging. To identify the cause of this aging. To identify, if possible, the most appropriate actions to correct the situation. In its simplest form diagnostic testing takes the form of a “Spot Test.” Most electri- cal maintenance professionals have made spot tests where a voltage is applied
12、to the insulation and a resistance is measured. The diagnosis in this case is limited to “the insulation is good” or “the insulation is bad.” But having made this diagnosis what do we do about it? Its a bit like going to the doctor with a bad cough and the doctor simply telling you, “Youve got a bad
13、 cough.” You wouldnt be happy to come away with only that information. You expect the doctor to examine you, carry out a few tests, and tell you why you have a bad cough and what to do about it to cure the cough. In insulation testing, a spot test on its own is the equivalent of the doctor telling y
14、ou that you are well or you are sick. Its minimal information. This is the sort of test that is typically applied to low-voltage circuits where the cost of a failure is low and equipment can be replaced easily and inexpensively. Since the equipment being tested is low voltage equipment, these tests
15、are typically performed using a 500 or 1000 V test voltage and will be familiar to all electrical maintenance person- nel. However, if the doctor records the results of his examination and compares them with those from previous visits, then a trend might be apparent which could lead to medication be
16、ing prescribed. Similarly, if insulation resistance readings are re- corded and compared with previously obtained readings, it may be possible to see a trend and to prescribe remedial actions if such are called for. Diagnostic insulation testing at voltages above 1 kV is an area that is less familia