1、MEGGER MEGGERCM300 MKII,CM400 MKII the black lead to Neutral, and the green lead to Earth (ground). 3.Select (M ) L-PE, L-N or N-PE as required. 4.Press either the Ior the TYPE key to display the test voltage. Press again until the required test voltage is displayed. 5.Press and hold the TEST key. 6
2、.Circuit resistance value is displayed. 7.Release the TEST button, but maintain connection to allow the test voltage to discharge. Power plug method The insulation resistance of an installation may be tested by using the plug terminated test lead at a convenient socket outlet. However:- a)The instal
3、lation must be isolated from the supply. b)The insulation test will incorporate the immediate circuit and any other circuit connected on the load side of the distribution board (D.B.). c)If a low reading is obtained, each circuit must be individually tested from the distribution board to locate the
4、fault. Operation (contd.) 14 After performing an insulation test, maintain connection to the circuit under test to allow the circuit to discharge. If voltage remains after a test, the instrument will normally display this as it is discharged. It must be verified that the test voltage has been discha
5、rged before moving onto the next test. When using the 2-wire lead set to measure insulation, always select (M ) L-N. The insulation will be measured between the two leads. 1.Disconnect Phase, Neutral and Earth from the D.B. 2.Insert the power plug into an installation socket on the isolated circuit
6、to be tested. 3.Select (M ) L-PE, L-N or N-PE as required. 4.Press either the Ior the TYPE key to display the test voltage. Press again until the required test voltage is displayed. 5.Press and hold the TEST key. 6.Circuit resistance value is displayed. 7.Release the TEST button, but maintain connec
7、tion to allow the test voltage to discharge. Method of measurement A current limited d.c. source is used, and the resistance is calculated from measurements of the voltage and current. The polarity of this d.c. source is as follows:- Range +ve terminal -ve terminal L-NNeutral (Black)Phase (Red) N-EN
8、eutralEarth L-EPhase (Red)Earth (Black) The voltage is only present when the test button is pressed. A measurement of the terminal voltage is made before the test and if this exceeds about 25 V the test is disabled. If d.c. voltage is detected across any of the terminals a discharge resistor is conn
9、ected across it. The reading is stable with a circuit capacitance less than 5 F. Loop Impedance measurement Loop impedance measurement of 0,01 up to 3.00 k can be made via installation sockets using the plug terminated test lead, or at any other convenient point on the installation using the two wir
10、e lead set. If Setting A is selected when using the plug terminated lead set, the polarity of the mains socket is immaterial. Line and Neutral will be swapped if necessary, and an indication given on the display. Setting b requires Line and Neutral to be fixed. The Installation Testers will measure
11、the loop resistance from the supply end of the standard test leads, allowing for their resistance. 15 Test results may be adversely affected by supply voltage fluctuations or electrical noise during measurement. It is recommended that tests are repeated and the results verified, if measurement resul
12、ts are considered abnormal. V o l t s Resistance- M 1000 V 500 V 250 V Insulation Test Voltage Phase to Neutral or Earth loop impedance measurement - Power plug method 1.Select (Loop) L-PE or L-N as required. 2.Insert the plug into an installation socket. 3.Supply voltage and polarity are displayed.
13、 4.Press the TEST key. 5.Measured loop value is displayed. On completion of this test, prospective fault current can be displayed by pressing the DISPLAY key. If desired the test can be repeated by pressing TEST again. Phase-Earth loop impedance measurement-Two wire method If an installation socket
14、is not available, use the the 2-wire lead set. 1.Select (Loop) L-PE. 2.Connect the red lead to phase and the black lead to earth. No connection to neutral is required. 3.Supply voltage is displayed. Note:- Though displayed, polarity indications are invalid with the two wire lead set and should be ig
15、nored 4.Press the TEST key. 5.Measured loop value is displayed. On completion of this test, prospective fault current can be displayed by pressing the DISPLAY key. If desired the test can be repeated by pressing TEST again. Bonded Metalwork Testing (1) This test is performed using the two wire lead
16、set. 1.Connect the black lead to the bonded metalwork. 2.Connect the red lead to phase. 3.Select (Loop) L-PE 4.Supply voltage is displayed. 5.Press the TEST key. 6.Measured resistance value is displayed. Bonded Metalwork Testing (2) This test can also be performed using the optional earth bond test
17、lead, allowing connection to an installation socket. 1.Connect the black flying test lead to the bonded metalwork. 2.Insert the power plug test lead into a socket (receptacle). 3.Select (Loop) L-PE. 4.Supply voltage is displayed. 5.Press the TEST key. 6.Measured resistance value is displayed. Operat
18、ion (contd.) 16 Automatic testing To aid rapid testing, the instruments can be set to start a test automatically when connected to the supply. This may be of use, for example, when using a clip and a probe. Select the range required and press the test key without the supply present. The instrument w
19、ill display 150 V and 300 V Nominal Voltage 110 V 230 V 400 V 3.Supply voltage is displayed. Note:- Though displayed, polarity indications are invalid with the 2- wire lead set and should be ignored 4.Press the TEST key. Test progress is displayed. 5.Measured loop value is displayed. If desired the
20、test can be repeated by pressing TEST again. Method of measurement The phase-earth, phase-neutral or phase-phase loop resistance can be measured. The instrument takes a current from the supply and measures the difference between the unloaded and loaded supply voltages. From this difference it is pos
21、sible to measure the loop resistance. The test current will vary from 15 mAto 40 A, depending on supply voltage and the loop resistance value. The test duration will depend on the loop resistance value. Possible sources of error The reading depends on a measurement of the supply voltage and therefor
22、e noise or transients caused by other equipment during the test could cause an error in the reading. One way to check for these is to do two tests and look for any difference in value. The instrument will detect some sources of noise and warn the user, where other instruments may give an incorrect r
23、eading. Any leakage current as a consequence of other appliances connected to the supply under test may affect the reading. If the Phase - Earth loop is being measured, this leakage may be due to filter capacitors etc. Operation (contd.) 18 RCD Testing The Installation Testers can test the operation
24、 of a variety of types of Residual Current Devices (RCD), measure the phase to earth loop resistance, and the contact voltage of the installation. Using an earth test spike, the earth resistance and fault voltage may be measured. If Setting A is selected when using the plug terminated lead set, the