1、nally been treated as a drying operation can become a rewind job. An insulation tester (commonly referred to as a “Megger,” although that is in fact a registered AVO trademark) overcomes these problems. Rigorous limiting of output cur- rent by a resistor network in the test circuit means that under
2、the lowered resistance as- sociated with deteriorated insulation, the test voltage will automatically drop to non-inju- rious levels. And an insulation test, instead of a simple pass/fail indication, provides an accurate reading of the resistance value. There can be no “near misses.” If the reading
3、he plethora of insulation test methods and procedures that appear in the lit- erature and product descriptions can seem bewildering to someone trying to establish a testing regime or meet an application. A thorough explanation of all of them, of course, is well beyond the scope of a single article,
4、but for a conve- nient organizing principle, one can refer to the Law of Diminishing Returns. That is to say, no single test can tell everything about a particular section of in- sulation or its associated apparatus, so that additional tests may be re- quired to isolate a problem or make a determina
5、tion. But the- ory must be balanced against practicality in order to avoid the wasted time and expense of mak- ing more and more tests for fewer and fewer added results. A proce- dure issued to customers by a lead- ing manufacturer of electric locomotives, GM Electro Motive Di- vision, illustrates t
6、his concept very well. Locomotives returned to shop for rou- tine scheduled maintenance were tradi- tionally tested by either/or 1 kV Megger insulation tests or high-potting, typically at 1080 VAC. While these tests caught most problems, the practice did not catch them all. There persisted annoying
7、and costly failures after some locomotives were returned to service. Why? High-potting is basically a crude test. Many rely on it because its dramatic re- sults (failure light and buzzer) tend to in- spire confi dence in the test, but therein lies the shortcoming. A high-pot makes a pass/fail determ
8、ination based on a trip set- ting for either breakdown or leakage cur- rent, or both. This may be set by the operator, or it may be factory-set by the manufacturer. It gives only an indication of the condition of the test item (in this case, a locomotive) at the time of the test. It has no predictiv