Biddle CB100_UG 电路图.pdf
《Biddle CB100_UG 电路图.pdf》由会员分享,可在线阅读,更多相关《Biddle CB100_UG 电路图.pdf(92页珍藏版)》请在收音机爱好者资料库上搜索。
1、 AVTM810130 Rev. A April 2002 Instruction Manual AVTM810130 for Capacitance And Dissipation Factor Bridge Catalog No. 810130 High Voltage Equipment Read the entire manual before operating. Aparato de Alto Voltaje Antes de operar este producto lea este manual enteramente. AVO International PO Box 900
2、7 Valley Forge, PA 19485-1007 U.S.A. Shipping Address: Valley Forge Corporate Center 2621 Van Buren Avenue Norristown, PA 19403 U.S.A RadioFans.CN 收音机爱 好者资料库 2 TABLE OF CONTENTS 1.0 GENERAL INFORMATION.6 1.1 GENERAL DESCRIPTION.6 1.2 CB100 FEATURES.6 1.3 SPECIFICATIONS.7 1.4 ACCESSORIES FURNISHED.8
3、1.5 ACCESSORIES AVAILABLE .8 1.6 CHANGES.9 1.7 WARRANTY.9 2.0 INSTALLATION.10 2.1 UNPACKING AND INSPECTION.10 2.2 PREPARATION FOR USE.10 2.3 LINE SUPPLY VOLTAGE.10 2.4 REPACKING AND SHIPMENT.10 3.0 OPERATING INSTRUCTIONS.11 3.1 PANEL CONTROLS AND OPERATING FUNCTIONS.11 3.1 PANEL CONTROLS AND OPERATI
4、NG FUNCTIONS (continued).12 3.2 SAFETY CONSIDERATIONS.13 3.3 GENERAL OPERATING INSTRUCTIONS FOR CB100.13 3.4 MEASUREMENT OF TWO WINDING TRANSFORMERS .17 A. Preparation for Test.17 B. Measurement of Insulation Power Factor.18 C. Recording of Identification and Test Data Using Test Sheet 01-100 and 02
5、-100 .20 D. Temperature Corrections.21 3.5 MEASUREMENT OF BULK OIL CIRCUIT BREAKER (O.C.B.).26 A. Preparation for Test.26 B. Measurement of Individual Bushings R.H. to 80% Storage: -40C to +65C. Temperature Coefficients: 0.02% of applicable accuracy spec. per C of both capacitance and dissipation fa
6、ctor. PHYSICAL: Instrument and accessories supplied with portable foam lined carrying case. Case has hinged opening from above with a lockable latch. Sizes: Model CB100 290W x 240H x 175D mm (11.5W x 9.5H x 7D in) Transport Case 430W x 375H x 330D mm (17W x 14.7H x 13D in) Weight: Instrument 5 kg (1
7、1 lbs) Shipping 11.8 kg (24 lbs) 1.4 ACCESSORIES FURNISHED Each instrument is supplied complete with: - two color coded leads-coaxial cable-10m long. - one color coded ground lead cable-10m long. - three wire line input cord. - one instruction-service manual. - one transport case. 1.5 ACCESSORIES AV
8、AILABLE 810132 Range Extension Adaptor 810133 Calibrator 810200 Oil Test Cell 810210 Oil Test Cell Heater 9 1.6 CHANGES Please note that this instrument is subject to continuous development and improvement. This instrument may therefore incorporate minor changes in detail from the information contai
9、ned herein. 1.7 WARRANTY Multi-Amp warrants this instrument sold by us or our authorized agents to be free from defects in material and workmanship for a period of 12 months from date of shipment. During the warranty period Multi-Amp will, at our option, repair or replace the instrument or part ther
10、eof which proves to be defective providing: 1. The instrument is returned properly packed and transportation prepaid with prior authorization from us or our appointed agent. 2. The instrument has not been altered, modified or repaired by unauthorized personnel and 3. That our examination discloses t
11、o our satisfaction that any improper operation or failure was not the result of improper use, negligence or accident, exceeding environmental limits, or connecting the instrument to incompatible equipment. This warranty is exclusive and is given and accepted in lieu of all other warranties, expresse
12、d or implied, and constitutes fulfillment of all our liabilities to the purchaser. Multi-Amp specifically disclaims the implied warranties of merchantability and fitness for a specific purpose. We assume no liability, in any event, for consequential damages, for anticipated or lost profits, for pers
13、onal injury due to use or accident, for incidental damages or loss of time or other losses incurred by the purchaser or any third party in connection with instruments covered by this warranty. 10 2.0 INSTALLATION 2.1 UNPACKING AND INSPECTION Prior to shipment this instrument was electrically tested
14、and mechanically inspected and found to meet specifications and be free of mechanical defects. After unpacking the instrument, visually inspect the instrument and accessories for damage. If evidence of damage is present, you must contact the carrier who transported the unit and file a claim in writi
15、ng. The shipping container and packing material should be retained for inspection by the carriers agent. Electrical operation as per section 3 should be checked as soon as possible after receipt. 2.2 PREPARATION FOR USE INSURE THAT THE APPARATUS TO BE TESTED IS CLEARED AND DE- ENERGIZED PRIOR TO TES
16、T. It is highly recommended that the user familiarize himself with the controls, functions and features detailed in section 3 prior to use. 2.3 LINE SUPPLY VOLTAGE This instrument is shipped from the factory for operation on either 120V, 60 Hz line or 220V, 50 Hz. 2.4 REPACKING AND SHIPMENT To insur
17、e proper shipment of this instrument it is recommended that the original reusable container and packing material be retained. If being returned for calibration or service please attach a card to the instrument specifying the owner, model and serial number and service required. 11 3.0 OPERATING INSTR
18、UCTIONS 3.1 PANEL CONTROLS AND OPERATING FUNCTIONS This section details and describes the operating features of the CB100 and is keyed in Figure 1 (next page). 1. Line Input Socket - Standard input for line cord provided. 2. Instrument On - Flipping this switch upwards activates the instrument, imme
19、diately sending test voltage to output BNC. 3. Power On Indicator - This red L.E.D. illuminates when instrument is energized. 4. Detector Phasing Switch - State of bridge balance of capacitance or dissipation factor selected. Null meter (5) is indicator for balance condition. 5. Null Meter - Indicat
20、or for balance condition of capacitance or dissipation factor. Detector phasing switch (4) determines which is being balanced. 6. Dissipation Factor Range Switch - The approximate magnitude of dissipation factor is first determined by this switch. 7. Dissipation Factor Dial - The precise value of di
21、ssipation factor is determined by this setting in conjunction with the D.F. range switch. 8. Capacitance Multiplier Switch - The approximate value of the capacitance being tested is determined with this switch. 9. Capacitance Switch - This switch determines the approximate value of capacitance being
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- Biddle CB100_UG 电路图
收音机爱好者资料库所有资源均是用户自行上传分享,仅供网友学习交流,未经上传用户书面授权,请勿作他用。



Marshall-9100-62-02-Schematic电路原理图.pdf


