1、Digital Loop Tester MEGGERLT7 User Guide Guide de lutilisateur Gebrauchsanleitung Gua del usuario NOTE THE INSTRUMENT MUST ONLY BE USED BY SUITABLY TRAINED AND COMPETENT PERSONS. Symbols used on the instrument Caution: refer to accompanying notes. Equipment protected throughout by Double Insulation
2、(Class II) Equipment complies with relevant EU Directives SAFETY WARNINGS Safety warnings and precautions must be read and understood before the instrument is used. They must be observed during use. Continuity of protective conductors and earthed equipotential bonding of new or modified installation
3、s must be verified before carrying out an earth fault loop impedance test. Exposed metalwork of an installation or equipment under test must not be touched. LT7 must not be connected across two phases of a 3 phase supply. The LCD neon voltage indicators cannot reveal a Neutral - Earth reversal. Loop
4、 impedance 50 V when performing a 3 wire test (L-PE and N - PE neonsactivated). 3)Electrical noiseexceeds rejection level on low current range. (displayed). 4)Voltage is out of range. Flashing VOL and actual Voltage displayed. 5)Supply frequency out of limits (flashing HZ displayed). 6 )Thermal prot
5、ection device operates on h i g h current range ( and d i s p l a y e d ) . Low Current (Auto) measurement (0,1 or 1 resolution) This mode measures Live to Earth loop impedance via installation sockets. Live to Earth or Live to Neutral loop impedance can also be measured using the optional dual lead
6、 test set. The measurement sequence takes 11 seconds. Residual Current Devices (R.C.D.s) 30mA will not trip. LT7 is supplied as standard with a display resolution of 0,1 . In areas of exceptional electrical noise, and where improved repeatability may be desired, it is possible to change the display
7、resolution to 1 in the following manner:- 1)Turn rotary switch to the OFF position. 2)Press and hold the Retest push button whilst turning the rotary selector switch to any other position. 3)Still holding the Retest button, the display will cycle between 1 and 0,1 resolution. 4)Release the Retest bu
8、tton when the desired resolution is displayed. To operate LT7:- 1) Turn rotary switch to Auto. 2)Connect LT7 by mains cord, or using the dual test lead firmly connect red test probe to Live and the black test probe to Neutral or to Protective Earth (ground). Mains (line) voltage is displayed. 3)Test
9、 progress is indicated by a sequential display of vertical bars. Refer to Safety Warnings before using the instrument RadioFans.CN 收音机爱 好者资料库 4)Loop impedance value is displayed directly in . (2 kdisplayed if resistance exceeds 2 k). High Current (20 ) measurement (0,01 resolution) This mode measure
10、s L i v e t o E a r t h loop impedance via installation sockets o r t h e L i v et oE a r t h or the L i v et oN e u t r a l loop impedance using the optional dual lead test set. N o t e: This mode may cause RCDs to trip. The measurement sequence takes 5 seconds. 1 )Turn rotary switch to 2 0 . 2 )Co
11、nnect LT7 by mains cord, or using the dual test lead firmly connect red test probe to Live and the black test probe to Neutral or to Protective Earth (ground). Mains (line) voltage is displayed. 3 )Test progress is indicated by a sequential display of vertical bars. 4 )Loop impedance value is displa
12、yed directly in . N o t e : Any measurement 20 displayed if resistance exceeds 20). High Current (PSCC) m e a s u r e m e n t In this mode, LT7 displays the Prospective Short Circuit Current (calculated at the nominal supply voltage of 230V divided by loop impedance). This mode can be used for L i v
13、 e to Earthconnection via unprotected installation sockets, o r for Live toE a r t h , o r L i v e to Neutral connection on unprotected circuits using the optional lead set. T h i s mode may cause RCDs to trip. The measurement sequence takes 5 seconds. 1)Turn rotary switch to PSCC. 2)Plug in the LT7
14、, or firmly connect red test probe to Live and black test probe to Protective Earth (ground) or to Neutral. Mains (line) voltage is displayed. 3)Test progress is indicated by a sequential display of vertical bars. 4)PSCC value displayed directly in kA. (20kA displayed if value exceeds 19,9kA). Earth
15、 Bond Testing By using the earth bond test lead available as an optional extra, the LT7 can measure the quality of Equipotential bonding within an installation. 1) Turn rotary switch to Auto or 20 . 2) Firmly connect the flying lead probe to the metalwork to be tested and plug the LT7 into a conveni
16、ent installation socket. 3)Reading displayed will consist of socket supply (live conductor) impedance plus the impedance of the equipotential earth bonding. SPECIFICATION Ranges: 20 (23Anominal)0,01 - 19,9 2% 3 digits (230 V supply) 5% 6 digits (110 V supply) 200 /2k (15mAnominal) 1 -1,99k 2% 1 digi
17、t (230 V supply) 5% 2 digits (110 V supply) When set to 0,1 resolution2% 3 digits (230 V supply) (3 digits at 1 typical) PSCC (23Anominal)0,01 - 0,99 kA 1,0 - 19,9 kA Note: Calibration includes the test leads and plug. To maintain accuracy, these must not be changed. See note overleaf. Nominal Syste
18、m Voltage:110 V / 230 V at 50 Hz Voltage Accuracy:2% 2 digits (when L-PE neon indicates). Power supply:4 x 1,5 V Alkaline cells IEC LR6 type or 4 x 1,2 V NiCd or NiMHrechargeable cells Auto shut off:After 5 minutes of instrument inactivity Battery life: Typically 1200, one minute tests Low Battery I
19、ndicator:The symbol will appear when Alkaline battery cells are almost e x h a u s t e d . Note: Battery cells should not be left in an instrument which may remain unused for extended periods of time. Display:3 digit L.C.D. Temperature Range: Operating:-5C to 40C (0 - 90% RH non Condensing) Storage:
20、-25C to 65C (0 - 95% RH non Condensing at 4 0 C ) Thermal Protection:Thermal cut-out will prevent overheating caused by repetitive testing on highcurrent range. Safety: Meets the requirements for double insulation to IEC1010-1(1995) EN61010 (1995) at 230 V installation Category III*, without the nee
21、d for separately fused test leads. If required, fused test leads are available as an optional accessory. *Relates to transient overvoltage likely to be found in fixed installation wiring. Fuses:- Internal 10A (F) 440 V 10kA ceramic HBC - Mains power cord fused plug (when applicable): 10 Amp fuse to
22、BS1362 E.M.C:In accordance with IEC 61326 including amendment No.1 Note:Overvoltage spikes may cause a reset to the original power On state before reverting to normal operation. Environmental Protection:IP54 Dimensions:220 mm x 92 mm x 55 mm Weight:1200g (including leads, case & battery cells) Clean
23、ing:Wipe disconnected instrument with a clean cloth dampened with soapy water or Isopropyl Alcohol (IPA). ACCESSORIES SuppliedPart number User Guide6172-087 Power cord test lead with 3 pin plug to BS1363/A6231-601 or Power cord test lead with CEE 7/7 plug6231-593 Dual test lead with probe6231-591 Te
24、st-&-carry case 6420-092 Optional Test Lead Set red/balck6220-437 Crocodile clip, black, for use with dual test lead6280-284 Earth bond test lead with probe and 3 pin plug 6231-586 to BS1363/A Fused probe and clip set (2 probes and 3 clips) 1000 V max.10A fuse6180-405 Power cord The power cord suppl