1、CABLE FAULT LOCATOR MEGGERCFL510F (TDR1000/2) User Guide MEGGER RadioFans.CN 收音机爱 好者资料库 RadioFans.CN 收音机爱 好者资料库 SAFETY WARNINGS Although this tester does not generate any hazardous voltages, circuits to which it can be connected could be dangerous due to electric shock hazard or due to arcing (initi
2、ated by short circuit). While every effort has been made by the manufacturer to reduce the hazard, the user must assume responsibility for ensuring his, or her own safety. For use on energised systems rated up to 300V Installation Category III* the fused clip set AVO Part Number 6111-218, must be us
3、ed. * Relates to the transient over voltages likely to be met in fi xed wiring installations. 4mm plug to BNC Adaptor: This 4mm plug to BNC adapter is intended for use with telecomm network cables only, it is not designed or intended for direct connection to an energised mains supply. However, in no
4、rmal use it may be subject to telecom network voltages (TNV) as defi ned by IEC 60950 3rd edition (1999-04). The BNC plug and socket are, by necessity, accessible. The outer sheath for this connector is normally at SELV levels, however under single fault conditions it may carry hazardous voltages. T
5、he operator must therefore verify that the accessible plug or socket is at SELV levels prior to touching, or alternatively wear appropriate insulated gloves. The instrument should not be used if any part of it is damaged. Test leads, probes and crocodile clips must be in good order, clean and with n
6、o broken or cracked insulation. Check that all lead connections are correct before making a test. A Fused Lead Set must be used to connect to energised live systems. Refer to the accessories section for options. Disconnect the test leads before accessing the battery compartment. Refer to operating i
7、nstructions for further explanation and precautions. Safety Warnings and Precautions must be read and understood before the instrument is used. They must be observed during use. 3 NOTE THE INSTRUMENTS MUST ONLY BE USED BY SUITABLY TRAINED AND COMPETENT PERSONS. RadioFans.CN 收音机爱 好者资料库 Contents Safet
8、y Warnings3 Introduction5 General description Battery replacement User Controls and Display8 Layout and functions Operation10 General Testing procedure Line Feed Connection to cable under test Measuring distance to fault Menu TX Null Velocity Factor Pulse widths Techniques to improve accuracy Care a
9、nd Maintenance15 Specifi cations16 Symbols used on the instrument are: Caution:Referto accompanying notes. Equipment protected throughout by double or reinforced nsulation. Instrument fl ash tested to 3.7kV rms. Equipment complies with current EU directives. 4 Introduction Thank you for purchasing t
10、he CFL510F cable fault locator. Before attempting use of your new instrument please take the time to read this user guide, ultimately this will save you time, advise you of any precautions you need to take and could prevent damage to yourself and the instrument. The CFL510F is an advanced instrument
11、 capable of identifying a wide range of cable faults. The instrument uses a technique called Pulse Echo (also known as Time Domain Refl ectometry or TDR). A pulse is launched into a cable from one end. This can be on either a pair of conductors, or a conductor and the screen. The pulse travels down
12、the cable at a velocity determined by the insulation between the conductors and this resistance to the fl ow of the pulse is characterised as impedance for the cable. Any changes in cable impedance will cause a proportion of the pulse to be refl ected. The pulse velocity is normally described as a f
13、raction of the speed of light and is called the Velocity Factor. By measuring the time between the transmitted pulse and the reception of the reflected pulse, and multiplying this by the speed of light and the velocity factor, the actual distance to the refl ection point can be established. Refl ect
14、ions are caused by changes in the cables characteristic impedance, such as poor joints or discontinuities. Faults showing an impedance higher than that of the cables normal impedance will cause a refl ection of the same polarity, i.e.positive, whilst faults with an impedance lower than that of the c
15、able will cause an inverse negative going reflection. Matched cable terminations absorb all the pulse hence no “end of cable” refl ection will occur, the cable appearing endless. Open or short circuits will refl ect all the pulse and a large refl ection will be displayed. At an open or short circuit
16、 all the transmitted energy is refl ected and the TDR will not see the cable beyond that fault. As a pulse travels down a cable, the size and shape of that pulse is gradually attenuated by the cable. The pulse reduces in amplitude and becomes more elongated or stretched. The level of attenuation (or
17、 losses) is determined by the cable type, the condition of the cable and any connections along its length. The limit of how far you can see is determined by the point beyond which you will not be able to see or distinguish a reflection. To help identify small reflections, especially at greater dista
18、nce the CFL510F has an adjustable gain setting. By increasing the gain small refl ections become more obvious. The CFL510F can be used on any cable consisting of 5 Introduction at least two insulated metallic elements, one of which may be the armouring or screen of the cable. The CFL510F has interna
19、l matching networks to allow testing of 25, 50, 75 and 100 cables. (These typically correspond to power, coaxial data and data/telecoms cable). By selecting the TDR impedance closest to that of the cable under test, maximum power can be transmitted into the cable allowing long cables to be tested. T
20、he velocity factor of the TDR must be adjusted to match that of the cable under test, allowing an accurate distance measurement to be read directly from the instrument. Where the VF of a cable is not known, but the length is, the cursor can be set to the end of the cable and the VF on the TDR adjust
21、ed until the correct cable length is displayed. Other confi guration settings include changing the distance units between metres and feet, changing the propagation velocity units between a ratio and a distance per microsecond. Display contrast is fully adjustable to compensate for all viewing condit
22、ions. A backlight aids viewing in low ambient light conditions. The instrument can be powered by manganese- alkali, nickel-cadmium or nickel-metal-hydride batteries. All cells must be of the same type. 6 When the low battery symbol appears in the display window the cells are nearly exhausted and sho
23、uld be replaced as soon as possible. Use alkaline cells IEC LR6 (AA) 1.5V or 1.2V rechargeable cells only. To install or replace the cells, switch the instrument off. Disconnect the test leads, loosen the battery cover retaining screws and remove the cover. Lift out and disconnect the battery holder
24、. Replace the cells, ensuring that correct polarity is observed (shown on the battery holder). Incorrect battery cell polarity can cause electrolyte leakage resulting in damage to the instrument Refi tting the battery holder is the reverse of removing it. 7 Battery fi tting and replacement User cont