1、RadioFans.CN 收音机爱 好者资料库 RadioFans.CN 收音机爱 好者资料库 RadioFans.CN 收音机爱 好者资料库 Part _ 12436 Rev. 0 INSTRUCTION MANUAL INSTRUCTION MANUAL For For CIRCUIT BREAKER TEST SETS CIRCUIT BREAKER TEST SETS MODEL CB-71XX MODEL CB-71XX SERIAL NO. It is essential that this instruction book be read thoroughly before pu
2、tting the equipment in service. It is essential that this instruction book be read thoroughly before putting the equipment in service. Part _ 12436 Rev. 0 IMPORTANT The information and data contained within this instruction manual are proprietary with AVO MULTI-AMP Corporation. The equipment describ
3、ed herein may be protected by one or more U.S. letters patent. AVO MULTI-AMP specifically reserves to itself all rights to such proprietary information as well as all rights under any such patent, none of which is waived by the submission of this instruction manual to anyone. The recipient, if a Gov
4、ernment agency, acknowledges that this instruction book and the equipment described were procured with Limited Rights to technical data as described in ASPR 9-203 (b). Copyright AVO MULTI-AMP Corporation, 1991 TABLE OF CONTENTS TABLE OF CONTENTS SECTION PAGE SPECIFICATIONS.Bulletin CB FUNCTION OF CO
5、NTROLS Maximum output. Position 8. The OUTPUT SELECTOR switch is interlocked with the output initiating circuit. Depressing the switch to change positions operates the interlock and de-energizes the output. VERNIER CONTROL Provides fine adjustment of the output between steps of the OUTPUT SELECTOR s
6、witch. INITIATE Button: Energizes the output and starts the timer. EXT. INIT. An external switch can be plugged into (External Initiate) Jack: this jack to provide remote initiation of the test set. The jack is wired in parallel with the INITIATE button. CONTACTS Binding Posts: These binding posts f
7、acilitate connection to a set of contacts on the device under test to monitor contact opening or closure. The timer stops and the test set is de-energized when the device operates. Part _ 12436 Rev. 0 2 CONTINUITY Panel Lamp and Jack: This jack is wired in series with a green panel lamp so that cont
8、act action or circuit continuity can be monitored. Circuit Breaker: Functions as the input POWER ON/OFF switch and also provides short-circuit and overload protection. POWER ON Panel Lamp: Indicates when the circuit breaker is ON and input power is available. AMMETER RANGE Switch: Selects the full s
9、cale range of the ammeter. AMMETER: Indicates output current. CONTROL FUSE (1.5A): Protects the control circuit. TIMER: This is a specially designed electronic digital timer for indicating the elapsed time of the test in either seconds or cycles. The timer automatically starts at the beginning of ea
10、ch test and stops when the device under test operates. TIMER OPERATION SELECTOR Switch: This six-position switch selects which of the three modes of operation is to be used to control the output and timer operation. The three modes of operation are described below: (1) N.O. (Normally Open): When the
11、 device to be tested has normally open contacts (such as an overcurrent relay) this type of operation is used. In this position, the timer will run from the initiation of the test until closure of the contacts connected to the CONTACTS binding post. (2) N.C. (Normally Closed): When the device to be
12、tested has normally closed contacts (such as a multi-pole circuit breaker), this type of operation is used. In this position, the timer will run from the initiation of the test until the opening of the contacts connected to the CONTACTS binding post. Part _ 12436 Rev. 0 3 (3) C.A. (Current Actuator)
13、: When the device to be tested has no contacts other than those involved in the passing of test current (such as a single pole circuit breaker), this type of operation is used. In this position, the timer will run from the initiation of the test until the test circuit is interrupted. See Service Dat
14、a section for information on sensitivity and adjustment of current actuator The above three modes of operation can be used in either the MAINT. (maintained) or MOM. (momentary) positions. (1) MAINT. In this position, when the INITIATE button is pressed, the control circuit is sealed-in to maintain t
15、he output of the test set until the device under test operates. This is the normal position for timing tests. (2) MOM. In this position, the output of the test set is on only as long as the INITIATE button is held closed. This position is normally used when setting the test current prior to the timi
16、ng test. Part _ 12436 Rev. 0 4 AMMETER CIRCUIT:AMMETER CIRCUIT: The output current of Multi-Amp Circuit Breaker Test Sets is read on an ammeter connected to the output circuit by appropriate current transformers and an AMMETER RANGE switch. The desired full scale value of the ammeter is selected by
17、means of the AMMETER RANGE switch and by utilizing the correct common terminal. The proper common terminal must be utilized in order to connect the correct current transformer into the circuit. See SELECTION OF COMMON TERMINAL. The meter is a 4.5 inch square iron-vane instrument of 1% full scale acc
18、uracy. Whenever using an indicating instrument of full scale accuracy, the user should choose a range to give an indication as close to full scale as possible (upper 1/3 of scale). It should be noted that there is no relationship between the ammeter ranges and the rating of the output terminals. ANY
19、 AMMETER RANGE CAN BE USED WITH ANY OUTPUT TERMINAL. The ammeter is equipped with an adjustable pointer pre-set mechanism, by which means the ammeter pointer may be preset to any position on the scale and held there with no current in the meter circuit. This is a mechanical operation accomplished by
20、 means of an insulated knob on the front of the meter. It is used to overcome the inertia of the moving system of the meter so that currents of short duration can be set or read accurately. In use, the pointer is mechanically preset approximately 1/8 inch below the desired current. The device under
21、test is connected to the test set and the output is slowly increased while the INITIATE button is periodically pulsed. Some quivering of the pointer will be seen as the output current approaches the preset value. Continue to increase the output until the meter pointer lifts off the preset mechanism
22、and moves up scale to the desired test current. Hold the INITIATE button long enough to be certain the ammeter needle has stabilized. Part _ 12436 Rev. 0 5 INPUT AND OUTPUT CIRCUITS INPUT AND OUTPUT CIRCUITS INPUT:INPUT: INPUT VOLTAGE: INPUT VOLTAGE: Multi-Amp Circuit Breaker Test Sets are designed
23、to operate from any of several input voltages in order to accommodate the various voltages encountered by users in the field. It is necessary to change the input terminal connections to match the available input voltage. For all units except Model CB-7150, this change is made on a terminal board loc
24、ated inside the top access panel. On Model CB-7150, this terminal board is located inside the left hand door of the Instrumentation and Control section. It is recommended that the test set be disconnected from the source before changing input terminals. NOTE: On Model CB-7150, input voltages of 240