1、CLAMP-ON GROUND RESISTANCE TESTER DET10C/DET20C USERS MANUAL RadioFans.CN 收音机爱 好者资料库 EN 61010-2-032 CAT III 300V, CAT II 600V Pollution Degree 2 Definition of Symbols: Caution: Refer to Accompanying Documents Caution: Risk of Electric Shock Double Insulation RadioFans.CN 收音机爱 好者资料库 Table of Contents
2、 I. WARNING.1 II. FEATURES DESCRIPTION .1 III. CONTROLS DESCRIPTION .2 IV. LIQUID CRYSTAL DISPLAY.3 V. OPERATING INSTRUCTIONS.4 5-1. Ground Resistance Measurement .4 5-2. High and Low Alarm ( ).5 5-3. Ground/Leakage Current Measurement .7 5-4. Setting the Sampling Interval .7 5-5. Data Logging.8 5-6
3、. Downloading Data to a PC (DET20C only).8 5-7. Format of Down Loaded Data (DET20C only) .9 5-8. Reading the Data Stored in Memory.9 5-9. Clearing the Data Memory .10 5-10. Enable RS-232C output (DET20C only) .10 5-11. Installation of Megger Download Manager Software.11 5-12. Description of Megger D
4、ownload Manager Software.11 VI. PRINCIPLE OF OPERATION .12 VII. ELECTRICAL SPECIFICATION .14 VIII. GENERAL SPECIFICATIONS.15 IX. BATTERY REPLACEMENT.16 RadioFans.CN 收音机爱 好者资料库 I. WARNING 1. Use of rubber gloves is good safety practice even if the equipment is properly operated and grounded. 2. Safet
5、y is the responsibility of the operator. 3. Use extreme caution when using the instrument around energised electrical equipment. 4. Do not attempt to use the ground tester to twist or pry the ground electrode or ground wire away from the equipment being grounded. 5. All metal objects or wires connec
6、ted to the electrical system should be assumed to be lethal until tested, the grounding system is no exception. II. FEATURES DESCRIPTION The clamp-on ground resistance tester enables the user to measure the ground resistance of a ground rod without the use of auxiliary ground rods. The clamp-on grou
7、nd resistance tester is used in multi-grounded systems without disconnecting the ground under test. 1 III. CONTROLS DESCRIPTION 1 2 3 4 5 6 9 8 7 1. Jaw Assembly: Encircle electrode or ground rod. No air gap is allowed between the two jaw halves. 2. Hold Button: Maintains last measurement on display
8、 3. Rotary Switch: Power on and function selection. 4. LCD panel 5. “ REC ” button: Function dependant on mode. Starts either data logging, single measurement recording, or data download to PC. Also used to increment a value in conjunction with FUNC button. 6. “ FUNC “button: Press to select “HI” (h
9、igh alarm), “LO” (low alarm), “SEC” (recording interval), “dL” (Data down load), “no” (Read Data) or “232” (RS-232C) 7. Jaw opening lever 8. Battery cover 9. RS-232C interface connection point (DET20C only) 2 IV. LIQUID CRYSTAL DISPLAY AP 1. Function Display current selected function or current reco
10、rd number. 2. Digits Display value from 0 to 9999 with decimal point. 3. Ohm Indicates resistance mode and alarm functions. 4. mA Indicates ground leakage current mode in mA or A 5. Indicates instrument is set at the alarm position. 6. NOISE: Indicates ground resistance tester senses noise or excess
11、ive current present in the ground electrode 7. Jaw Open Displayed if the jaws are opened during the measurement, this symbol and word OPEN will be shown in LCD. 8. Low Battery Indicates battery voltage is lower than required. 9. NO. Indicates the data record number in memory. 10. REC Indicates data
12、logging is in progress. 11. H Indicates “HOLD” function activated 12. AP Indicates Auto Power Off activated. Deactivate by holding down the REC button then turning on unit. 3 4 V. OPERATING INSTRUCTIONS 5-1. Ground Resistance Measurement 1. Open the jaws and make sure that the mating surfaces are cl
13、ean and free of dust, dirt or any foreign substance. 2. Snap the jaws a few times to ensure clean contact is made. 3. Turn the rotary switch to the position to power the instrument on. Do not clamp on to any conductor or open the jaws, as this is a self-calibration phase. 4. At power on in mode, the
14、 instrument will perform a self-calibration for optimum accuracy. Users must wait for self-calibration to be complete before use. During the self-calibration phase, the LCD will show CAL7, CAL6, CAL5, CAL4, CAL 3, CAL2, and CAL1. 5. When the ground tester is ready, a beep will be heard. 6. Place the
15、 clamp around the electrode or ground rod to be measured. Operate the jaws a few times for better accuracy. 7. Read the value of Rg (ground resistance) from LCD. Note: For better measurement: 1. Operate the jaws a few times before powering on to clear mating surfaces. 2. Do not clamp on to any condu
16、ctor during power up (point 3 above). 3. Operate the jaws a few times after clamping around the ground electrode. Note: If self-calibration does not complete (The instrument will continue the process until a successful self-calibration is achieved): 1. Check the jaw mating surfaces. If there is any
17、dirt, dust, or any foreign substance, clean the surfaces. 2. Ensure the jaws are not open during self-calibration. Note: Noise present in the electrode or ground rod. If there is excessive current or over 30V noise in the ground rod, a symbol of “NOISE” will be shown in LCD. Under these conditions,
18、the reading is no longer accurate. We recommend the current flow is measured before a resistance reading is taken. Note: If jaws are opened during a measurement, a symbol of “OPEN” will be displayed on the LCD. 5-2. High and Low Alarm ( ) 1. Set the rotary switch to the position. 2. Press the FUNC b
19、utton to select “HI“ or “LO” alarm. The present value of High or Low alarm will be shown in the lower row of LCD. 3. Press the button to increment the value by 1 ohm. If the button is held down, the rate of increment accelerates. The value can be set from 0 ohm to 1550 ohm and then OL. The value wil
20、l roll over to 1(HI) or 0 (LO) if the set value in incremented past OL. 4. Once the value is set, press the FUNC button several times until the upper row LCD does not show any letters. 5. When the rotary switch is set at the position the instrument will compare the measured value with the high and l
21、ow values. If the measurement is higher than the HI value, the unit will beep and show “HI - in the upper row of LCD. If the current measurement is lower than the LO value, the unit will beep and show “LO- “ in the upper row of LCD. 5 6 NOTE: If the HI value is set at OL, or the LO value is set at 0
22、, the ALARM function is disabled. The HI or LO value can be disabled individually NOTE: The HI value cannot be lower than the LO value. Similarly the LO value cannot be higher than the HI value. HI value will be adjusted to LO value plus 1 if roll-over occurs. The maximum value of LO value is HI val
23、ue minus 1. NOTE: If data logging is in progress, the beeper will be disabled to save battery power. However, the LCD displays the warning letters of “HI“ or “LO“ if an alarm condition occurs NOTE: The values for the high and low alarm are stored in the memory. The values will be active when the uni