1、Wee MEGGER Te s t e r WM6 catalog No. 21805-3 User Guide Guide de lutilisateur G e b r a u c h s a n l e i t u n g Gua del usuario MEGGER RadioFans.CN 收音机爱 好者资料库 SAFETY WARNINGS #The circuit must be de-energized and isolated BEFORE connections are made for any test. #Do not touch the circuit during
2、an insulation test. #After insulation tests, capacitive circuits MUST be allowed to discharge BEFORE disconnecting the test leads. #Test leads, including prods and crocodile clips, must be in good order; clean and having no broken or cracked insulation. #Replacement fuses must be of the correct type
3、 and rating. Refer also to page 8 for further explanations and other precautions. The warnings and precautions must be read and understood before the instrument is used. They must be observed during use. 2 NOTE This instrument must only be used by suitably trained and competent persons. RadioFans.CN
4、 收音机爱 好者资料库 CONTENTS Safety Warnings2 General Description4 Applications4 Specification5 Accessories7 Operation8 Warning8 Preliminary checks8 Fuse replacement8 Insulation testing9 Continuity testing9 Using the Insulation Tester10 Preventive maintenance10 Insulation Testing concepts11 Mode dEmploi12 B
5、etriebsanleitung14 Instrucciones de Uso16 Setting-up Procedure18 Repair and Warranty19 3 RadioFans.CN 收音机爱 好者资料库 GENERAL DESCRIPTIONAPPLICATIONS The WM6 MEGGERInsulation and Continuity Tester is a completely self contained instrument designed to give rapid and accurate measurement of insulation resi
6、stance and continuity resistance. The WM6 uses a low voltage hand-cranked a.c. brushless generator as the power supply. This generator is easy to turn and is connected to a rectifier and d.c. to d.c. converter to provide the test voltage. The WM6 uses a moving coil meter with taut band suspension, w
7、hite scales on a black scale plate and an orange dayglow pointer. An electronic circuit is employed to produce a four decade calibrated scale for insulation resistance measurement from 0 to 200 M. Two shrouded sockets are provided in the side of the case for the test leads and a slider switch select
8、s either insulation or continuity tests (M or ). The case is robust, made of ABS plastic, and the generator handle folds neatly against it when not in use. The WM6 is intended for the direct measurement of insulation resistance and continuity of domestic and industrial wiring, cables, transformers,
9、motors, generators, electrical machinery and appliances. Because the WM6 is self-powered it is suitable for use during installation and commissioning work as well as for service and maintenance applications. Note: The cover of this instrument has been given an antistatic treatment which should be ef
10、fective for many months. If in the course of time the cover is found to retain electrostatic charges, it should be re-treated with a suitable antistatic solution. 4 SPECIFICATION WM6 Rangesinsulation0200 M and continuity0100 Terminal Voltageinsulation range600 V on Open Circuit (d.c.)continuity rang
11、e800 mV approx. Terminal Voltage atinsulation range500 V + 10% 5% 1 M Load (d.c.) Terminal Currentinsulation range1,3 mA approx. on Short Circuitcontinuity range55 mA approx. Voltage Stabilityinsulation range1% 160 r.p.m. to 240 r.p.m. Ripple Content at 160 r.p.m.insulation range500 mV pk-pk approx.
12、 on Open Circuit Accuracy1,5 mm (0,060 in) from any marked position on the scale when measured against standard resistors. Temperatureoperating10 C to +50 C storage20 C to +70 C Flash Test2,3 kV a.c. r.m.s. Voltage Source (d.c.)Brushless a.c. hand-cranked generator with rectifier and d.c. to d.c. co
13、nverter. 5 SPECIFICATION Fuse1 A 20 x 5 mm ceramic Dimensions131 x 98 x 61 mm (51/8x 37/8x 23/8in) Weight650 g (1 lb 7 oz) Terminal Voltage Characteristics 6 WM6 SPECIFICATIONACCESSORIES Illustrations of Typical Scales (full size) WM6 SUPPLIED WITH THE INSTRUMENT Test lead set including shrouded cro
14、codile clips User GuidePart No. 6171-685 Test Record Card (5 supplied)Part No. 6172-111 AVAILABLE AS AN OPTIONAL EXTRA A leather test-and-carry case with a special compartment for test leadsPart No. 6420-088 Test Lead set red/blackPart No. 6220-437 Test Record Card (Pack of Twenty)Part No. 6111-216
15、7 OPERATION W A R N I N G 1 .The circuit under test m u s t be de-energized and isolated before insulation or continuity tests are m a d e . 2 .When capacitive circuits have been tested allow a suitable time to elapse before disconnecting the test leads, for the circuit to discharge. 3 .Instruments
16、used in dusty environments should be stripped and cleaned periodically. 4 .Do not leave the instrument exposed to direct heat from the sun for long periods. 5 .The instrument circuit contains a static sensitive device. If the instrument casing is opened for any reason (this will automatically invali
17、date any warranty covering the instrument), care must be exercised in handling the printed circuit board. This should be done in accordance with DEF STAN 59-98 and BS 5783 specifications for handling electrostatic sensitive devices. Printed circuit boards containing such devices are identified eithe
18、r by a yellow warning label or by a yellow legend and a large yellow dot on the p.c.b. (Initially the dot may not be included.) PRELIMINARY CHECKS Inspect the test leads to see that they have good unbroken insulation. Connect the red and black leads, terminated with the clips, to the red (+) and bla
19、ck () terminal sockets respectively in the side of the instrument case. Leave the leads coiled or twisted together, but ensure that their clips are not touching anything. Set the slider switch to the M position. Turn the generator handle at approximately 160 r.p.m. and observe the meter pointer, it
20、should rest over the (infinity) position on the scale. If it does not the test leads may be faulty and should be inspected more closely for damage. Replace them if necessary. Connect the test lead clips together and turn the generator handle again, the meter should read zero. If it indicates infinit
21、y or a high resistance value the leads may be open circuit and should be inspected further, replace if necessary. Shorting the leads together and obtaining a zero reading also proves that the instrument is working. To check that the fuse in the continuity circuit is intact, leave the test leads conn
22、ected together and set the slider switch to the position. Turn the generator handle again, the reading obtained should be zero (or very nearly so). If the reading is beyond full scale on the range the fuse has ruptured and should be r e p l a c e d . 8 FUSE REPLACEMENT The fuse is held in a screw-ty
23、pe holder. To change a fuse, use a screwdriver to release the centre part of the holder containing the fuse. Replace with a 1 A 20 x 5 mm ceramic fuse part no. 25413-286. An alternative fuse should not be used as the fuse resistance will affect the lower continuity readings. INSULATION TESTING After
24、 connecting the test leads to the instrument and making the preliminary checks as detailed above, set the slider switch to M. With the circuit to be tested isolated, connect the test leads as follows: ( a ) for insulation tests to earth connect the red lead to earth or frame of the equipment, and th