1、5kV Digital Insulation Tester MEGGER BM25 User Guide Guide de lutilisateur Gebrauchsanleitung MeterCenter Gua del usuario Telephone: +1 480-659-8351 Toll Free in U.S. 800-230-6008 MEGGER BM25 - July 98 22/6/00 10:31 am Page 1 RadioFans.CN 收音机爱 好者资料库 Application Notes Preventive Maintenance17 Insulat
2、ion Testing Concepts18 Application of Test Techniques Short time or Spot Test19 Polarization Index (PI) Test19 Dielectric Discharge (DD) Test20 Stress considerations21 Specification 22 Accessories25 Appendix 1 - Results displayed at the end of each test26 Appendix 2 - RS 232 Output information displ
3、ay examples28 Repair and Warranty29 Symbols used on the instrument Caution: Refer to accompanying notes. Risk of electric shock. Equipment complies with relevant EU Directives Equipment protected throughout by Double Insulation (Class II). ContentsGuide de lutilisateur - p30Gebrauchsanleitung - s50G
4、ua del usuario - p70 2 Safety Warnings 3 General Description 4 Test Mode Summary5 Features and Controls6 Battery Charging7 Operation Testing Precautions8 Performing Tests - General9 Testing procedures10 Insulation Resistance Testing (R)10 Test Current measurement (I)10 Polarization Index Testing (PI
5、)10 Dielectric Discharge Testing (DD)11 Step Voltage Testing (SV)11 Factory settings12 Custom timed PI test12 Custom timed DD test12 Setting Custom Test Time values12 Using the Guard Terminal13 Measurements above 100 G 13 Fault Conditioning (BURN)14 Condition and Warning Indicators15 Data Download16
6、 BM25 - July 98 22/6/00 10:31 am Page 2 RadioFans.CN 收音机爱 好者资料库 3 SAFETY WARNINGS Safety Warnings and Testing Precautions must be read and understood before the instrument is used. They must be observed during use The circuit under test must be switched off, de-energised and isolated before test con
7、nections are made. The BM25 can generate up to 2 mA at 5000 V. Circuit connections must not be touched when HV is selected. Circuits must be discharged before disconnecting the test leads. In certain circumstances, break-down of the circuit under test could cause the instrument to terminate the test
8、, possibly causing a loss of display while the circuit remains energised. In this event, it is important that the circuit is allowed to discharge and the instrument is turned off before touching any connections. The test terminal area and charging panel recess should be kept in a dry, clean conditio
9、n. Replacement fuses must be of the correct type and rating. The instrument should not be used if any part of it is damaged. Refer to Testing Precautions on page 8 for further explanations and precautions. NOTE THE INSTRUMENT MUST ONLY BE USED BY SUITABLY TRAINED AND COMPETENT PERSONS. BM25 - July 9
10、8 22/6/00 10:31 am Page 3 RadioFans.CN 收音机爱 好者资料库 Battery capacity is continuously displayed by a segmented indicator. The indicator flashes when the battery requires recharging. Power is obtained from two parallel connected sealed rechargeable lead acid batteries. If either battery fails (or an int
11、ernal protection fuse ruptures) the instrument will continue to operate on the alternative battery. The battery is recharged by external 95 - 265V a.c., 50-60 Hz, or 12 V d.c.supply. Charging connections, mains power indicator and instrument protection fuses are located in a splashproof protected re
12、cess in the front panel. Specially designed lid hinges enable the lid to be removed and replaced as required, and will protect the lid from strain or damage by unclipping itself if unintentionally opened past its full extent. Design safety features include:- The flashing HV warning LED on the front
13、of the instrument , and the flashing H.V. symbols on the display remind the user that hazardous voltage is present when testing. External voltage 50 V displayed with flashing H.V. symbols on the display. Load automatically discharged at the end of a test, and decaying voltage ( 50 V) displayed. Inte
14、rlocked sliding cover to prevent simultaneous access of charging and test terminals. Test terminal sockets lock test leads into the case and prevent accidental disconnection. General Description 4 The BM25 is a compact, automated high voltage, battery powered instrument used to carry out Polarizatio
15、n Index, Step Voltage, and Dielectric Discharge tests as well as spot Insulation tests. The BM25 has a resistance measurement capability up to 5 T and leakage current measurement enables resistances up to 500 T to be measured. The design of the instrument takes full advantage of microprocessor techn
16、ology and features a large, clear liquid crystal display, combining digital and analogue readings of insulation resistance. Set nominal voltage options of 500 V, 1000 V, 2500 V and 5000 V are selectable. A variable output voltage setting provides a range of 25 V to 5000 V incremental in 25 V steps.
17、At switch on, the instrument carries out a calibration self check which automatically adjusts the measurement system. The calibration sequence inhibits any testing if the measurement system fails to meet preset limits. On starting a test, the HV warning LED on the front of the instrument flashes, to
18、gether with the display HV warning symbols. The integral timer starts automatically and displays minutes and seconds elapsed since the start of the test. The timer can be used to set the duration of a test, and will automatically stop the output voltage when the set time has expired. During a test,
19、measurements are automatically sent every 5 seconds via an isolated optical link to the RS 232 connector to enable downloading of the results to a computer. BM25 - July 98 22/6/00 10:31 am Page 4 final resistance value, and capacitance value. Custom timed DD values can be set if required (see Custom
20、 timed DD test). Step Voltage Testing (SV) This 5 minute test depends on the principle that an ideal insulator will produce identical resistance readings at all voltages. Conversely, an insulator which is being over stressed will show lower values at higher voltages. Operating at either 2,5 kV or 5
21、kV, the voltage steps up one fifth every minute, and successive measurements are taken. On completion, each of the 5 separate results are sequentially displayed followed by the capacitance value. Fault Conditioning (Burn) This low current feature is used to carry out continuous testing under breakdo
22、wn conditions. General Notes: 1) Acapacitance value reading is only available if the test has run for more than one minute, and the reading was not over-range. 2) Internal discharge resistors are automatically selected :- -At the end of a test. -If the instrument is switched off. -If an internal err
23、or is detected. Any voltage remaining on the terminals at the end of a test,will be displayed until it has decayed to less than 50 V. During a test output terminal voltage is displayed, together with flashing high voltage symbols, and the flashing red LED. Test Mode Summary 5 Insulation Resistance T
24、esting (R) This mode measures insulation resistance at the selected voltage to provide an instantaneous spot reading. Final test result is given sequentially with the corresponding leakage current and capacitance value. Test Current measurement (I) This mode measures insulation at the selected volta